Abstract Preview

ISO 5660-1:2015 specifies a method for assessing the heat release rate and dynamic smoke production rate of specimens exposed in the horizontal orientation to controlled levels of irradiance with an external igniter. The heat release rate is determined by measurement of the oxygen consumption derived from the oxygen concentration and the flow rate in the combustion product stream. The time to ignition (sustained flaming) is also measured in this test.

The dynamic smoke production rate is calculated from measurement of the attenuation of a laser light beam by the combustion product stream. Smoke obscuration is recorded for the entire test, regardless of whether the specimen is flaming or not.


General information

  • Status :  Published
    Publication date : 2015-03
  • Edition : 3
    Number of pages : 55
  • :
    ISO/TC 92/SC 1
    Fire initiation and growth
  • 13.220.50
    Fire-resistance of building materials and elements